﻿This parameter defines the value of the proportional band.

In heating control, the limits of the band are:

* difference of setpoint and half of the dead band
* difference of setpoint, half of the dead band and proportional band

In cooling control, the limits of the band are:

* sum of setpoint and half of the dead band
* sum of setpoint, half of the dead band and proportional band

If the value of the object "<Logic xx> Input Temperature" is included between the limits, a percentage control from 0% to 100% is set on output object.